16.1.7 SRZ (MODBUS RTU)

Communication Setting
Editor
Communication setting
Item
Connection Mode
Signal Level
Baud Rate
Data Length
Stop Bit
Parity
Target Port No.
SRZ
DIP switch
Switch
1
2
3
4
5
6
7
8
Slave address setting switch
Switch
C
* For connection to V9, the available address setting range is 0 to E (17 to 31).
Available Device Memory
The available setting range of device memory varies depending on the controller model. Be sure to set within the range
available for the controller to be used. Use [TYPE] when assigning indirect device memory for macro programs.
Device Memory
---
Setting
1 : 1 / 1 : n / Multi-link2 /
Multi-link2 (Ethernet) /
1 : n Multi-link2 (Ethernet)
RS-232C / RS-422/485
4800 / 9600 / 19200 / 38400 bps
None / Odd / Even
Z-TIO: 1 to 16
Z-DIO: 17 to 31
Setting
Contents
OFF
Baud rate: 19200 bps
ON
OFF
Data bit configuration
OFF
8 bits / without parity / 1 bit
ON
ON
Protocol: Modbus
OFF
-
OFF
-
Setting
0 to F
TYPE
00H
16.1 Temperature Controller/Servo/Inverter Connection
8 bits
1 bit
Default: 1
OFF, OFF: 4800 bps
ON, OFF: 9600 bps
OFF, ON: 19200 bps
ON, ON: 38400 bps
OFF, ON, ON: 8 bits / even /1 bit
ON, ON, ON: 8 bits / odd /1 bit
For Z-TIO, the number that is one greater than the set value is the address.
(Range: 1 to 16)
For Z-DIO, the number that is seventeen greater than the set value is the
address. (Range: 17 to 32
(Underlined setting: default)
Remarks
Remarks
(Underlined setting: default)
Remarks
*
)
Remarks
16-9