Fuji Electric Monitouch V9 Series Connection Manual page 334

Hide thumbs Also See for Monitouch V9 Series:
Table of Contents

Advertisement

PLC_CTL
Macro command "PLC_CTL F0 F1 F2"
Contents
Auto tuning
Lamp value setting
Lamp value read out
Setting data
Operation control
Manual operation
13.2 Temperature Controller/Servo/Inverter Connection
F0
n
Station number
n + 1
Command: 0
1 - 8
0 - 7: AT start channel No.
(PLC1 - 8)
10: Collective start at all channels
n + 2
11: Sequential start at all channels
12: Cancel
n
Station number
n + 1
Command: 1
n + 2
Bank No. / channel No.
1 - 8
n + 3
Lamp value
(PLC1 - 8)
Unit of time
0: Second
n + 4
1: Minute
2: Hour
n
Station number
n + 1
Command: 2
n + 2
Bank No. / channel No.
1 - 8
n + 3
Lamp value
(PLC1 - 8)
Unit of time
0: Second
n + 4
1: Minute
2: Hour
n
Station number
1 - 8
n + 1
Command: 3
(PLC1 - 8)
0: Save
n + 2
1: Initialize
n
Station number
n + 1
Command: 4
1 - 8
0: Control start
(PLC1 - 8)
n + 2
1: Control stop
n + 3
Channel No.
n
Station number
1 - 8
n + 1
Command: 5
(PLC1 - 8)
n + 2
Channel No.
F1 (= $u n)
Return data: Data stored from temperature controller to V series
13-47
F2
3
5
3
3
4
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents