8.1.12 XGT / XGI Series (Ethernet)

Communication Setting
Editor
Make the following settings on the editor. For more information, see "1.3.2 Ethernet Communication".
 IP address for the V9 unit
- When specified on the screen program:
[System Setting]  [Hardware Setting]  [Local Port IP Address]
- When specified on the V9 unit:
Local mode  [LAN Setting]
 Port number for the V9 unit (for communication with PLC)
[System Setting]  [Hardware Setting]  [PLC Properties]  [Communication Setting]
 IP address and port number (No. 2004 for TCP/IP or No. 2005 for UDP/IP) of the PLC
Register on the [PLC Table] in [System Setting]  [Hardware Setting]  [PLC Properties]  [Target Settings].
PLC
Go to [Standard Settings] in XG-PD and set the IP address.
The port numbers are 2004 for TCP/IP and 2005 for UDP/IP (both fixed).
For more information, refer to the PLC manual issued by the manufacturer.
Calendar
This model is equipped with a calendar function; however, the calendar data cannot be written from the V series. Thus, time
correction must be performed on the PLC side.
Available Device Memory
The contents of "Available Device Memory" are the same as those described in "8.1.10 XGT / XGI Series CNET".
8.1 PLC Connection
8-17