Communication setting
Item
Connection Mode
Signal Level
Baud Rate
Data Length
Stop Bit
Parity
Target Port No.
CR/LF
Inverter
Parameter No.
A500
S500
E500
F500J
F500
77
79
117
118
119
120
121
122
123
-
-
-
124
146
*1
When the value in the range from 0.1 to 999.8 is set:
If the V series does not start communication within the preset time, the inverter stops due to an alarm. This can be avoided by the
periodical reading setting.
*2
When the inverter, FR-A500, FR-E500 or FR-F500, is turned on with the settings of Pr.79 = 0 and Pr.146 = 9999, the inverter enters in the
PU operation mode.
When the inverter, FR-S500 or FR-F500J, is turned on with the settings of Pr.79 = 2 and n10 = 1, the inverter enters in the computer link
operation mode.
*3
In the case of FR-A500, FR-E500 or FR-F500, when the running frequency change and operation command specification are made on the
V series, select the PU operation mode. In the case of FR-S500 or FR-F500J, when the running frequency change and operation command
specification are made on the V series, select the computer link operation mode. If those settings are not made on the V series, set an
appropriate value according to the purpose of usage.
1 : 1 / 1 : n / Multi-link / Multi-link2 /
Multi-link2 (Ethernet) /
1 : n Multi-link2 (Ethernet)
RS-232C / RS-422/485
4800 / 9600 / 19200 bps
7 / 8 bits
1 / 2 bits
None / Odd / Even
None / CR / CRLF
Item
77
Parameter writing permission
79
Operation mode selection
n1
Communicating station number
n2
Baud rate
n3
Data length / stop bit length
n4
Parity check
n5
Communication retrial times
n6
Communication check intervals
n7
Wait time
n8
Operation command write
n9
Speed command write
n10
Link start mode selection
n11
CR/LF selection
*2
-
Frequency setting
9.2 Temperature Controller/Servo/Inverter Connection
Setting
0 to 31
Setting
0: Writing allowed when PU
operation stops
1: Writing prohibited
2: Writing allowed during
operation
*2
0 / 1 / 2 / 3 / 4 / 6 / 7 / 8
0 to 31
4800 / 9600 / 19200 bps
0: 8 bits / 1 bit
1: 8 bits / 2 bits
10: 7 bits / 1 bit
11: 7 bits / 2 bits
0: None
1: Odd
2: Even
0 to 10 / 9999
*1
0 / 0.1 to 999.8 / 9999
0 to 150 / 9999
0: Computer
1: External
0: Computer
1: External
0:
*2
1: Computer link operation mode
0: CR/LF not provided
1: CR provided, LF not provided
2: CR/LF provided
0 / 1 / 9999
9-59
(Underlined setting: default)
Remarks
(Underlined setting: default)
Setting Example
2: Writing allowed during operation
*3
1: PU operation
*3
2: External operation
0
19200 bps
1: 8 bits / 2 bits
2: Even
9999:
The inverter does not stop even if a
communication alarm occurs.
9999: Communication check stop
9999: Can be set with the
communication data
0: Computer
0: Computer
1: Computer link operation mode
1: CR provided, LF not provided
9999