15-20
15. Panasonic
PLC
Make PLC settings using the programming tool "FPWIN GR7".
For more information, refer to the PLC manual issued by the manufacturer.
FP7 configuration
Built-in
ET-LAN
Calendar
This model is equipped with a calendar function; however, the calendar data cannot be written from the V series. Thus, time
correction must be performed on the PLC side.
Available Device Memory
The available setting range of device memory varies depending on the PLC model. Be sure to set within the range available for
the PLC to be used. Use [TYPE] when assigning indirect device memory for macro programs.
DT
(data register)
X
(external input)
Y
(external output)
R
(internal relay)
L
(link relay)
LD
(link register)
T
(timer/contact)
C
(counter/contact)
P
(pulse relay)
E
(error report relay)
SD
(system data)
SR
(system relay)
IN
(direct input)
OT
(direct output)
UM
(unit memory)
TS
(timer/set value)
TE
(timer/elapsed value)
CS
(counter/set value)
CE
(counter/elapsed value)
I
(index register)
Setting Item
Local IP address
Basic information
Subnet mask
on communication
Default gateway
Operation mode
Connection usage
Open system
(server/client)
Open system
(automatic/manual)
Communication mode
User connection
Local port No.
information
settings
Target port No.
Unused connection time
Target port setting method
Target IP address
Device Memory
Set the IP address of the PLC.
Set the subnet mask of the PLC.
Set the default gateway of the PLC.
MEWTOCOL-7
Use
Server connection (target station as desired) / server connection
(target station specified)
Open automatically
UDP/IP / TCP/IP
Set the port number of the PLC (8000 to 65535).
Port number of the V9
(communication mode: TCP/IP, open system (server/client):
Not required for server connection (target station as desired))
0
Specify the IP address (IPv4).
IP address of the V9
(communication mode: TCP/IP, open system (server/client):
Not required for server connection (target station as desired))
TYPE
00H
*1
01H
WX as word device; X0 to X1F and X70 to X9F: read only
02H
WY as word device; Y0 to Y9, Y13, Y15 to Y1F, Y70 to Y9F: read only
03H
WR as word device, including special relays
*1
04H
WL as word device
05H
*1
09H
*1
Read only
0AH
*1
Read only
*1
0BH
Read only
0CH
Read only
0DH
Read only
0EH
WS as word device, read only
0FH
WI as word device, read only
*2
10H
WO as word device
11H
*2
*1
12H
Double-word
*1
13H
Double-word
14H
*1
Double-word
*1
15H
Double-word
16H
Double-word
Setting
Remarks
*1
*1
*2
*1