Fuji Electric Monitouch V9 Series Connection Manual page 320

Hide thumbs Also See for Monitouch V9 Series:
Table of Contents

Advertisement

13.2.3 E5AN/E5EN/E5CN/E5GN
Communication Setting
Editor
Communication setting
Connection Mode
Signal Level
Baud Rate
Data Length
Stop Bit
Parity
Target Port No.
Temperature Controller
E5CN/E5SAN/E5EN
Communication level setting
Level
Communication
level
Adjustment level
*1
When writing setting data from the V9, set "ON" for the "communication writing" setting.
E5GN
Communication level setting
Level
Communication
level
Adjustment level
*1
When writing setting data from the V9, set "ON" for the "communication writing" setting.
Item
1 : 1 / 1 : n / Multi-link2 / Multi-link2 (Ethernet) /
4800 / 9600 / 19200 / 38400 / 57600 bps
Displayed
Character
PSEL
U-no
bps
LEn
Sbit
Prty
CMWT
Displayed
Character
U-no
bps
LEn
Sbit
Prty
CMWT
13.2 Temperature Controller/Servo/Inverter Connection
Setting
1 : n Multi-link2 (Ethernet)
RS-232C / RS-422/485
7 / 8 bits
1 / 2 bits
None / Odd / Even
0 to 31
Setting Data
Protocol selection
Communication unit No.
Baud rate
Data length
Communication stop bit
Parity
*1
Communication writing
Setting Data
Communication unit No.
Baud rate
Data length
Communication stop bit
Parity
*1
Communication writing
(Underlined setting: default)
Remarks
(Underlined setting: default)
Setting
CompoWay/F
0 to 31
4800 / 9600 / 19200 / 38400 / 57600 bps
7 / 8 bits
1 / 2 bits
None / Odd / Even
OFF / ON
(Underlined setting: default)
Setting
0 to 31
4800 / 9600 / 19200 bps
7 / 8 bits
1 / 2 bits
None / Odd / Even
OFF / ON
13-33