Application Guide | iC7 Series Industry
P 2.2.1.16 Power Limit Motor Delay
Set the delay before the selected response is triggered after the drive has reached the power limit.
Default Value:
Parameter Type:
Parameter
2364
Number:
Data Type:
REAL
P 2.2.1.17 Power Limit Generator Response
Select the response for running within power limit after the time delay set.
Default Value:
0 (No response)
Parameter
2367
Number:
Data Type:
UINT
The following are the selections for the parameter.
Selection Number
Selection Name
0
No response
1
Info
10
Fault
P 2.2.1.18 Power Limit Generator Delay
Set the delay before the selected response is triggered after the drive has reached the power limit.
Default Value:
Parameter Type:
Parameter
2365
Number:
Data Type:
REAL
6.3.3.2
Cooling Fan Control (Menu Index 2.2.2)
P 2.2.2.1 Main Fan Minimum Speed
Set the minimum speed of the main cooling fan.
Default Value:
Parameter Type:
Parameter
2932
Number:
Data Type:
REAL
P 2.2.2.2 Internal Fan Minimum Speed
Set the minimum speed of the internal cooling fan.
94
| © 2024.05
Range (0 — 65000)
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
Selection Description
The event is ignored.
The event is logged in the event log.
The drive issues a fault and coasts the motor.
Range (0 — 65000)
Unit:
Access Type:
Range (0 — 100)
Unit:
Access Type:
Parameter Descriptions
s
Read/Write
Selection
–
Read/Write
s
Read/Write
%
Read/Write
AB480436531518en-000601 / 136R0283