Application Guide | iC7 Series Industry
Select the digital input for the Start Enable command with a negative reference. If this parameter is not active, the drive will be stopped
while reference is negative.
Default Value:
Parameter
1602
Number:
Data Type:
UINT
6.6.7.3
DC Start (Menu Index 5.6.2)
P 5.6.2.1 DC Start Time
Set the duration of the current injection during DC start.
Default Value:
Parameter Type:
Parameter
2264
Number:
Data Type:
REAL
P 5.6.2.2 DC Start Current Rise Time
Set the time to ramp the current from 0 to the specified injection level.
Default Value:
Parameter Type:
Parameter
2265
Number:
Data Type:
REAL
P 5.6.2.3 DC Start Current
Set the DC current in % of nominal motor current. This current is injected during the DC start time.
Default Value:
Parameter Type:
Parameter
2263
Number:
Data Type:
REAL
Synchronous Motor Start (Menu Index 5.6.3)
6.6.7.4
P 5.6.3.1 Sync. Motor Start Mode
Set the synchronous motor initial postion handling.
Default Value:
1 (Rotor angle detection)
Parameter
2322
Number:
Data Type:
UINT
The following are the selections for the parameter.
© 2024.05
Parameter Type:
Unit:
Access Type:
Range (0 — 10000)
Unit:
Access Type:
Range (0 — 100)
Unit:
Access Type:
Range (0 — 1000)
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
AB480436531518en-000601 / 136R0283 |
Parameter Descriptions
Selection
Read/Write
s
Read/Write
s
Read/Write
%
Read/Write
Selection
Read/Write
183