Download Print this page

Danfoss iC7 Series Application Manual page 150

Hide thumbs Also See for iC7 Series:

Advertisement

Application Guide | iC7 Series Industry
Select the response for exceeding the limit.
Default Value:
9 (Fault, ramp to coast)
Parameter
5225
Number:
Data Type:
UINT
The following are the selections for the parameter.
Selection Number
Selection Name
3
Warning
9
Fault, ramp to coast
10
Fault
Temp. 6 Protection (Menu Index 5.2.3.7)
6.6.3.3.7
P 5.2.3.7.1 Temp. 6 Input
Select the temperature sensor input for the temperature protection.
Default Value:
Parameter
5226
Number:
Data Type:
UINT
P 5.2.3.7.2 Temp. 6 Limit 1
Set the temperature level for issuing a warning.
Default Value:
120
Parameter
5227
Number:
Data Type:
REAL
P 5.2.3.7.3 Temp. 6 Limit 2
Set the temperature level for issuing a protection response.
Default Value:
150
Parameter
5228
Number:
Data Type:
REAL
P 5.2.3.7.4 Temp. 6 Limit 2 Response
Select the response for exceeding the limit.
Default Value:
9 (Fault, ramp to coast)
150
| © 2024.05
Parameter Type:
Unit:
Access Type:
Selection Description
The drive issues a warning.
Issues a fault, ramps down, and coast.
The drive issues a fault and coasts the motor.
Parameter Type:
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
Parameter Type:
Parameter Descriptions
Selection
Read/Write
Selection
Read/Write
Range (-300 — 300)
°C
Read/Write
Range (-300 — 300)
°C
Read/Write
Selection
AB480436531518en-000601 / 136R0283

Advertisement

loading
Need help?

Need help?

Do you have a question about the iC7 Series and is the answer not in the manual?

Questions and answers