Download Print this page

Output Filter (Menu Index 3.5) - Danfoss iC7 Series Application Manual

Hide thumbs Also See for iC7 Series:

Advertisement

Application Guide | iC7 Series Industry
Selection Number
Selection Name
1
Fault, ramp to coast
2
Derate
P 3.4.4 Thermal Switch Input
Select the digital input terminal for the thermal switch.
Default Value:
Parameter
3414
Number:
Data Type:
UINT
P 3.4.5 Power Stabilizer Gain
Set the controller gain for power stabilization. The power stabilizer dampens possible resonance with the grid. If set to -1 the value is
selected automatically, if set to 0 the controller is disabled.
Default Value:
-1
Parameter
3415
Number:
Data Type:
REAL
P 3.4.6 Power Stabilizer Bandwidth
Set the controller bandwidth for power stabilization.
Default Value:
100
Parameter
3416
Number:
Data Type:
REAL

Output Filter (Menu Index 3.5)

6.4.6
P 3.5.1 Output Filter Type
Select the output filter type.
Default Value:
0 (None)
Parameter
5501
Number:
Data Type:
UINT
The following are the selections for the parameter.
108
| © 2024.05
Selection Description
Issues a fault, ramps down, and coast.
The drive issues a fault, continues operation, and derates to
protect the filter.
Parameter Type:
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
Parameter Descriptions
Selection
Read/Write
Range (-1 — 500)
%
Read/Write
Range (1 — 10000)
%
Read/Write
Selection
Read/Conditional Write
AB480436531518en-000601 / 136R0283

Advertisement

loading
Need help?

Need help?

Do you have a question about the iC7 Series and is the answer not in the manual?

Questions and answers