Application Guide | iC7 Series Industry
Select the output indicating if the DC-link voltage is within range.
Default Value:
–
Parameter
2311
Number:
Data Type:
UINT
Filters & Brake Chopper Status (Menu Index 3.1)
6.7.2.3
P 3.1.1 Brake Power
Shows the power dissipated in the brake resistor.
Default Value:
NA
Parameter
2933
Number:
Data Type:
REAL
P 3.1.2 Average Brake Power
Shows the average power dissipated in the brake resistor, calculated over 120 s.
Default Value:
NA
Parameter
2934
Number:
Data Type:
REAL
P 3.1.3 AHF Capacitor Connected
Shows if the advanced harmonic filter (AHF) capacitor is connected.
Default Value:
NA
Parameter
5410
Number:
Data Type:
BOOL
Motor Status (Menu Index 4.1)
6.7.2.4
P 4.1.1 Motor Current
Shows the actual motor current.
Default Value:
NA
Parameter
9000
Number:
Data Type:
REAL
P 4.1.2 Relative Motor Current
Shows the actual motor current in % of the nominal motor current.
266
| © 2024.05
Parameter Type:
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
Parameter Descriptions
Selection
–
Read/Write
Range (0.00 — \*)
kW
Read Only
Range (0.00 — \*)
kW
Read Only
Range (False — True)
–
Read Only
Range (0 — \*)
A
Read Only
AB480436531518en-000601 / 136R0283
Need help?
Do you have a question about the iC7 Series and is the answer not in the manual?
Questions and answers