Application Guide | iC7 Series Industry
Select the input or a predefined fixed value for the feedback.
Default Value:
–
Parameter
6027
Number:
Data Type:
UINT
P 5.10.4.6 Feedback 1 Conversion
Select a conversion function for the feedback.
Default Value:
0 (Linear)
Parameter
6009
Number:
Data Type:
UINT
The following are the selections for the parameter.
Selection Number
Selection Name
0
Linear
1
Quadratic
P 5.10.4.7 Feedback 2 Type
Select the type of feedback.
Default Value:
0 (Feedback disabled)
Parameter
6022
Number:
Data Type:
UINT
The following are the selections for the parameter.
Selection Number
Selection Name
0
Feedback disabled
1
Analog Feedback Terminal
2
Fieldbus Feedback
P 5.10.4.8 Feedback 2 Maximum Scaling
Set the maximum scaling value of the feedback.
Default Value:
100
Parameter
6017
Number:
242
| © 2024.05
Parameter Type:
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
Selection Description
The fieldbus reference will be scaled linearly.
The fieldbus reference will be scaled quadraticaly (ref^2).
Parameter Type:
Unit:
Access Type:
Selection Description
Use feedback value from the analog input.
Use feedback value from the fieldbus.
Parameter Type:
Unit:
Parameter Descriptions
Selection
–
Read/Write
Selection
–
Read/Write
Selection
–
Read/Write
Range (-1000000 — 1000000)
CustomProcessUnit
AB480436531518en-000601 / 136R0283
Need help?
Do you have a question about the iC7 Series and is the answer not in the manual?