Application Guide | iC7 Series Industry
Automatic: In this mode, the drive automatically switches between LO and HO1 depending on the load conditions.
l
170
160
150
140
130
120
110
100
90
-1 0 1 2 3 4
5 6 7 8 9 10 11 12
LO
Figure 57: Overload Modes
Table 26: Selection Descriptions
Selection Name
Automatic Mode
Low Overload Mode (LO)
90
| © 2024.05
170
160
150
140
130
120
110
100
90
-1 0 1 2 3 4
5 6 7 8 9 10 11 12
HO1
Selection Description
Automatically switches between the modes Low Overload (LO) and High Overload (HO1).
For applications running at a non-varying or slowly varying load, where a limited overload capabil-
ity is required. This mode is typically used in applications with a variable torque load. The low over-
load profile allows the drive to run at 110% load for a minimum of 1 minute every 10 minutes. Typi-
cal applications where the low overload profile is used are:
• Fans
• Centrifugal pumps
• Blowers and aerators
• Screw compressors
Parameter Descriptions