Application Guide | iC7 Series Industry
Parameter
2301
Number:
Data Type:
UINT
P 4.1.22 Extended Motor Speed Output
Select an output for the motor speed signal. The scale of the signal is -200...200% of the nominal speed.
Default Value:
–
Parameter
2309
Number:
Data Type:
UINT
P 4.1.23 Motor Power Output
Select an output for the motor power signal. The scale of the signal is 0–100% of the nominal power.
Default Value:
–
Parameter
2305
Number:
Data Type:
UINT
P 4.1.24 AMA Progress
Shows the progress of the Automatic Motor Adaptation (AMA).
Default Value:
NA
Parameter
429
Number:
Data Type:
REAL
P 4.1.26 Motor Temperature
The analog temperature sensor has exceeded the configured value.
Default Value:
NA
Parameter
1630
Number:
Data Type:
REAL
P 4.1.28 Rs Measured
When a Rs measurement has been stored for use after drive power recycle, the value is shown here; otherwise it is zero.
Default Value:
NA
Parameter
433
Number:
Data Type:
REAL
© 2024.05
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
AB480436531518en-000601 / 136R0283 |
Parameter Descriptions
–
Read/Write
Selection
–
Read/Write
Selection
–
Read/Write
Range (0 — 100)
%
Read Only
Range (-300 — 300)
°C
Read Only
Range (0 — 100000)
Ω
Read Only