P 4.5.5 Motor Thermistor Input
Select an input for the motor thermistor feedback.
Default Value:
–
Parameter
2839
Number:
Data Type:
UINT
P 4.5.6 Motor Thermistor Response
Select the response to a motor thermistor event.
Default Value:
9 (Fault, ramp to coast)
Parameter
2846
Number:
Data Type:
UINT
The following are the selections for the parameter.
Selection Number
Selection Name
3
Warning
9
Fault, ramp to coast
10
Fault
P 4.5.7 Motor Temperature Input
Select the input for the motor temperature sensor.
Default Value:
–
Parameter
2847
Number:
Data Type:
UINT
P 4.5.8 Motor Temperature Warning Level
Set the temperature level for issuing a warning.
Default Value:
120
Parameter
2848
Number:
Data Type:
REAL
P 4.5.9 Motor Temperature Fault Level
Set the temperature level for issuing a fault. The response will be ramp down and coast.
Default Value:
150
136
| © 2024.05
Parameter Type:
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
Selection Description
The drive issues a warning.
Issues a fault, ramps down, and coast.
The drive issues a fault and coasts the motor.
Parameter Type:
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
Parameter Type:
Parameter Descriptions
Selection
–
Read/Write
Selection
–
Read/Write
Selection
–
Read/Write
Range (-300 — 300)
°C
Read/Write
Range (-300 — 300)