Application Guide | iC7 Series Industry
Enable/disable the port-mirroring function for network troubleshooting with a network analyzer tool.
Protocols (Menu Index 10.3)
6.11.3
General Settings (Menu Index 10.3.1)
6.11.3.1
P 10.3.1.2 Fieldbus Profile
Select the fieldbus profile. The selection affects the interpretation of the control word and status word.
Default Value:
101 (iC Speed Profile)
Parameter
1301
Number:
Data Type:
UINT
The following are the selections for the parameter.
Selection Number
Selection Name
101
iC Speed Profile
201
PROFIdrive Standard Telegram 1
302
CiA402 Velocity Mode
P 10.3.1.3 Fieldbus Fault Response
Select the behavior when a fieldbus fault occurs.
Default Value:
1 (Info)
Parameter
1303
Number:
Data Type:
UINT
The following are the selections for the parameter.
Selection Number
Selection Name
1
Info
3
Warning
9
Fault, ramp to coast
10
Fault
P 10.3.1.4 No Fieldbus Connection Response
Select the response in case there is no fieldbus connection.
Default Value:
1 (Info)
340
| © 2024.05
Parameter Type:
Unit:
Access Type:
Selection Description
The fieldbus control word and status word are interpretated
according the iC Speed Profile definition.
The fieldbus control word and status word are interpretated
according to the PROFIdrive Standard Telegram 1 standard.
The fieldbus control word and status word are interpreted
according to the CiA402 Velocity Mode standard.
Parameter Type:
Unit:
Access Type:
Selection Description
The event is logged in the event log.
The drive issues a warning.
Issues a fault, ramps down, and coast.
The drive issues a fault and coasts the motor.
Parameter Type:
Parameter Descriptions
Selection
Read/Write
Selection
Read/Write
Selection
AB480436531518en-000601 / 136R0283