Download Print this page

External Event (Menu Index 5.2.2) - Danfoss iC7 Series Application Manual

Hide thumbs Also See for iC7 Series:

Advertisement

Application Guide | iC7 Series Industry
Set a delay before the cooling monitor issues a fault. Only valid if fault is selected.
Default Value:
3
Parameter
2401
Number:
Data Type:
REAL
P 5.2.1.3 Cooling Monitor Response
Select the response to a missing cooling monitor signal. The response is selected for both stopped and running states.
Default Value:
2 (Warning, Fault after Timeout while
running)
Parameter
2402
Number:
Data Type:
UINT
The following are the selections for the parameter.
Selection Number
Selection Name
0
Warning while running
1
Warning
2
Warning, Fault after Timeout while
running
3
Warning and Fault after Timeout while
running

External Event (Menu Index 5.2.2)

6.6.3.2
Events can be issued via an external signal with the parameters of the External Event parameter group. The event can be delayed with
parameters 5.2.2.9 External Event 1 Delay and 5.2.2.10 External Event 2 Delay.
P 5.2.2.1 External Event 1 Input
Select an input for the external event.
Default Value:
Parameter
4557
Number:
Data Type:
UINT
P 5.2.2.3 External Event 1 Response
Select the response to an external event.
Default Value:
9 (Fault, ramp to coast)
142
| © 2024.05
Parameter Type:
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
Selection Description
The drive issues a warning if the drive is in running state.
Drive issues a warning immediately.
Drive issues a warning immediately, and if the drive is running,
the warning escalates into a fault after a timeout.
When stopped, no response is given. When running, the drive
issues a warning immediately. The warning escalates into a fault
after a timeout.
Parameter Type:
Unit:
Access Type:
Parameter Type:
Parameter Descriptions
Range (0 — 100)
s
Read/Write
Selection
Read/Write
Selection
Read/Write
Selection
AB480436531518en-000601 / 136R0283

Advertisement

loading
Need help?

Need help?

Do you have a question about the iC7 Series and is the answer not in the manual?

Questions and answers