Data Type:
REAL
P 5.9.2.5 Speed Limit Mode Torque Ctrl.
Select the speed limiting mode during torque control.
Default Value:
0 (Pos./Neg. Speed Limit)
Parameter
2332
Number:
Data Type:
UINT
The following are the selections for the parameter.
Selection Number
Selection Name
0
Pos./Neg. Speed Limit
1
Speed Limit Setpoint
2
Window around Speed Limit Setpoint
P 5.9.2.6 Lower Window Limit
Set the window size towards the positive speed direction.
Default Value:
Parameter Type:
Parameter
2333
Number:
Data Type:
REAL
P 5.9.2.7 Upper Window Limit
Set the window size towards the negative speed direction.
Default Value:
Parameter Type:
Parameter
2334
Number:
Data Type:
REAL
P 5.9.2.26 Speed Limit Setpoint
Set the variable speed limit setpoint in torque mode. This is used when fixed speed limits are not desired.
Default Value:
50
Parameter
1336
Number:
Data Type:
REAL
P 5.9.2.27 Speed Limit Setpoint Ramp Time
© 2024.05
Access Type:
Parameter Type:
Unit:
Access Type:
Selection Description
Limit between positive and negative speed limit.
Limit between +/- speed limit setpoint.
Limit window around torque mode speed limit.
Range (0 — 10)
Unit:
Access Type:
Range (0 — 10)
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
AB480436531518en-000601 / 136R0283 |
Parameter Descriptions
Read/Write
Selection
Read/Conditional Write
Hz
Read/Write
Hz
Read/Write
Range (0 — 1000)
Hz
Read/Write
225