Application Guide | iC7 Series Industry
Parameter
1123
Number:
Data Type:
REAL
Ramp 4 (Menu Index 5.8.6.5)
6.6.9.7.6
P 5.8.6.5.1 Ramp 4 Type
Select the ramp type.
Default Value:
0 (Linear Ramp)
Parameter
1128
Number:
Data Type:
UINT
The following are the selections for the parameter.
Selection Number
Selection Name
0
Linear Ramp
1
S-Ramp
P 5.8.6.5.2 Ramp 4 Accel. Time
Set the acceleration time from 0 to nominal motor speed.
Default Value:
5
Parameter
1104
Number:
Data Type:
REAL
P 5.8.6.5.3 Ramp 4 Decel. Time
Set the deceleration time from nominal motor speed to 0.
Default Value:
5
Parameter
1108
Number:
Data Type:
REAL
P 5.8.6.5.4 S-Ramp 4 Accel. Increase Time
Set the ramp acceleration increase time for S-ramp.
Default Value:
1
Parameter
1112
Number:
Data Type:
REAL
212
| © 2024.05
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
Selection Description
Use linear ramp.
Use S-ramp ramp reducing torque changes.
Parameter Type:
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
Parameter Descriptions
s
Read/Write
Selection
–
Read/Write
Range (0 — 10000)
s
Read/Write
Range (0 — 10000)
s
Read/Write
Range (0 — 10000)
s
Read/Write
AB480436531518en-000601 / 136R0283
Need help?
Do you have a question about the iC7 Series and is the answer not in the manual?
Questions and answers