Application Guide | iC7 Series Industry
Parameter
2337
Number:
Data Type:
UINT
The following are the selections for the parameter.
Selection Number
Selection Name
1
Fault
2
Automatically derate
P 1.3.2 Missing Grid Phase Response
Select the response after detection of a missing grid phase.
Default Value:
1 (Fault)
Parameter
2338
Number:
Data Type:
UDINT
The following are the selections for the parameter.
Selection Number
Selection Name
1
Fault
2
Automatically derate
3
Warning
P 1.3.3 Undervoltage Protection
Enables the undervoltage protection. The drive trips when the grid voltage is 20% below the selected voltage class level. The voltage
class is defined in parameter "2.2.1.1 Unit Voltage Class".
Default Value:
1 (Enabled)
Parameter
2344
Number:
Data Type:
BOOL
The following are the selections for the parameter.
Selection Number
Selection Name
0
Disabled
1
Enabled
84
| © 2024.05
Unit:
Access Type:
Selection Description
The drive issues a fault and stops.
The drive continues operation with derated performance.
Parameter Type:
Unit:
Access Type:
Selection Description
The drive issues a fault and stops.
The drive continues operation with derated performance.
The drive issues a warning.
Parameter Type:
Unit:
Access Type:
Selection Description
Disables the function.
Enables the function.
Parameter Descriptions
–
Read/Write
Selection
–
Read/Write
Selection
–
Read/Write
AB480436531518en-000601 / 136R0283