Application Guide | iC7 Series Industry
Select an input for toggling between the 2 speed reference sources selected, when operating in advanced control and toggling logic is
used. A low signal selects the 1st source and high signal selects the 2nd source.
Default Value:
–
Parameter
1941
Number:
Data Type:
UINT
P 5.5.6.2.4 Adv. Torque Reference Source
Select the torque reference sources for when the drive operates in advanced control. Select 2 sources to combine them into 1 reference
value.
Default Value:
[2,0]
Parameter
1929
Number:
Data Type:
UINT
The following are the selections for the parameter.
Selection Number
Selection Name
0
None
2
Fieldbus reference
3
Reference 1 input
4
Reference 2 input
5
Preset reference
9
Logic Reference
P 5.5.6.2.5 Adv. Torque Reference Logic
Select how to form the torque reference out of the 2 inputs when operating in advanced control.
Default Value:
0 (Source 1)
Parameter
1919
Number:
Data Type:
UINT
The following are the selections for the parameter.
Selection Number
Selection Name
0
Source 1
1
Source 2
2
Sum
178
| © 2024.05
Parameter Type:
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
Selection Description
No source selected equals a 0 value.
Use reference from the fieldbus.
Use the reference from I/O reference 1.
Use the reference from I/O reference 2.
Use reference from the preset reference.
Use reference from Logic.
Parameter Type:
Unit:
Access Type:
Selection Description
Use value from source 1 only.
Use value from source 2 only.
Add references from source 1 and 2 together.
Parameter Descriptions
Selection
–
Read/Write
Selection
–
Read/Write
Selection
–
Read/Write
AB480436531518en-000601 / 136R0283
Need help?
Do you have a question about the iC7 Series and is the answer not in the manual?
Questions and answers