Download Print this page

Danfoss iC7 Series Application Manual page 287

Hide thumbs Also See for iC7 Series:

Advertisement

Application Guide | iC7 Series Industry
Parameter
1402
Number:
Data Type:
UINT
Auto Reset (Menu Index 6.4.4)
6.7.4.2
The automatic reset function enables the resetting of events without the need for a manual reset operation. This function is enabled with
parameter 6.4.4.1 Auto Reset.
When the function is enabled, a timer starts when an event requiring a reset is first triggered. An automatic reset is attempted at the end
of each time interval. If any event requiring a reset is still active, the automatic reset attempt does not succeed, and the timer continues
running. Once the maximum number of automatic reset attempts is reached, the automatic reset function stops, and a manual reset is
required to clear the events.
If all events are reset (through either an automatic or manual reset), the function resets the number of attempts and stops the timer. The
next event to trigger will begin a new cycle.
Before activating any automatic fault reset functions or changing limit values, make sure that no dangerous situations can
occur after restart. If the auto reset function is activated, the device connected to the drive output starts automatically after an
automatic fault reset.
A small set of events cannot be reset by the auto reset functionality, either because of safety reasons or because the events are
critical for the lifetime of the drive.
P 6.4.4.1 Auto Reset
Enables the automatic resetting of events.
Default Value:
False
Parameter
1405
Number:
Data Type:
BOOL
The following are the selections for the parameter.
Selection Number
Selection Name
0
Disabled
1
Enabled
P 6.4.4.2 Auto Reset Max Attempts
Set the maximum number of automatic resets that is allowed before a manual reset is required. 0 means the drive will auto reset infinite
times. Some events can not be auto reset due to hardware protection or for safety reasons.
Default Value:
3
© 2024.05
Unit:
Access Type:
  NOTICE
  NOTICE
Parameter Type:
Unit:
Access Type:
Selection Description
Disables the function.
Enables the function.
Parameter Type:
Parameter Descriptions
Read/Write
Selection
Read/Write
Range (0 — 20)
AB480436531518en-000601 / 136R0283 |
287

Advertisement

loading
Need help?

Need help?

Do you have a question about the iC7 Series and is the answer not in the manual?

Questions and answers