Application Guide | iC7 Series Industry
Data Type:
REAL
P 5.2.3.5.4 Temp. 4 Limit 2 Response
Select the response for exceeding the limit.
Default Value:
9 (Fault, ramp to coast)
Parameter
5221
Number:
Data Type:
UINT
The following are the selections for the parameter.
Selection Number
Selection Name
3
Warning
9
Fault, ramp to coast
10
Fault
6.6.3.3.6
Temp. 5 Protection (Menu Index 5.2.3.6)
P 5.2.3.6.1 Temp. 5 Input
Select the temperature sensor input for the temperature protection.
Default Value:
–
Parameter
5222
Number:
Data Type:
UINT
P 5.2.3.6.2 Temp. 5 Limit 1
Set the temperature level for issuing a warning.
Default Value:
120
Parameter
5223
Number:
Data Type:
REAL
P 5.2.3.6.3 Temp. 5 Limit 2
Set the temperature level for issuing a protection response.
Default Value:
150
Parameter
5224
Number:
Data Type:
REAL
P 5.2.3.6.4 Temp. 5 Limit 2 Response
© 2024.05
Access Type:
Parameter Type:
Unit:
Access Type:
Selection Description
The drive issues a warning.
Issues a fault, ramps down, and coast.
The drive issues a fault and coasts the motor.
Parameter Type:
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
Parameter Type:
Unit:
Access Type:
AB480436531518en-000601 / 136R0283 |
Parameter Descriptions
Read/Write
Selection
–
Read/Write
Selection
–
Read/Write
Range (-300 — 300)
°C
Read/Write
Range (-300 — 300)
°C
Read/Write
149
Need help?
Do you have a question about the iC7 Series and is the answer not in the manual?
Questions and answers