Delta AS Series Programming Manual page 278

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

Instruction code
FB_PN
Device
DX
DY
S
Data type
S
Symbol
Explanation
1.
When the value in the accumulative register switches from 1 to 0, the FB_PN instruction keeps the value 1 in the
accumulative register for a scan cycle. After the second scan cycle is finished, the value in the accumulative register
changes to 0.
2.
The previous state of the contact is stored in the bit device S. Do not use S repeatedly in the program. Otherwise,
the wrong execution result appears.
3.
Use FB_PN only in function blocks.
Example
Instruction
LD
M0
AND
M1
FB_PN
D0.0
OUT
Y0.0
Timing diagram
M0
M1
Y0 .0
Operand
S
X
Y
M
S : For internal use
Operation
Contact A of M0 is loaded.
Contact A of M1 is connected in series.
The circuit is falling edge-triggered.
The coil Y0.0 is driven.
One scan cycle
One scan cycle
C ha pt er 5 Bas ic I ns t r uc t i ons
Triggering the circuit on the falling edge.
SM
S
T
Function
C
HC
D
5 - 2 1
5_