Delta AS Series Programming Manual page 272

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

Instruction code
PLS
Device
DX
DY
D
Data type
D
Symbol
Explanation
1.
When the conditional contact switches from OFF to ON, the PLS instruction is executed, and the device D sends out
a pulse for a scan cycle.
2.
Do not use the PLS instruction in function blocks.
3.
ISPSoft V3.06.01 supports data type D and the BOOL type variable for declaration.
Example
When X0.0 is ON, M0 is ON for a pulse time. When M0 is ON, Y0.0 is set to ON.
Timing diagram
X0.0
On e sc an c y c le
M0.0
Y0.0
Operand
D
X
Y
M
SM
D : Specified device
PLS
C ha pt er 5 Bas ic I ns t r uc t i ons
Function
Rising-edge output
S
T
C
HC
D
5_
5 - 1 5