06 Protection Parameters

Low Voltage Level
06-00
Settings 230V models:
 Set the Low Voltage (Lv) level. When the DC bus voltage is lower than Pr.06-00, a Lv fault is
triggered, and the drive stops output and the motor coasts to a stop.
 If the Lv fault is triggered during operation, the drive stops output and the motor coasts to a stop.
There are three Lv faults: LvA (Lv during acceleration), Lvd (Lv during deceleration), and Lvn (Lv
in constant speed) that are triggered according to the status of acceleration or deceleration. You
must press RESET to clear the Lv fault. The drive automatically restarts if you set to restart after
momentary power loss (refer to Pr.07-06 Restart after Momentary Power Loss and Pr.07-07
Allowed Power Loss Duration for details).
 If the Lv fault is triggered when the drive is in STOP status, the drive displays LvS (Lv during stop),
which is not recorded, and the drive restarts automatically when the input voltage is higher than
Pr.06-00 + Lv return level (as listed below).
Lv Return Level
Frame A–D
Frame E–H
Frame A–D (including D0): 150.0–220.0 V
Frame E and above: 190.0–220.0 V
460V models:
Frame A–D (including D0): 300.0–440.0 V
Frame E and above: 380.0–440.0 V
575V models: 420.0–520.0 V
690V models: 450.0–660.0 V
230V models
30V
DC
40V
DC
12.1-06-1
Chapter 12 Descriptions of Parameter SettingsC2000 Plus
 You can set this parameter during operation.
Default:
DC
DC
DC
DC
DC
DC
460V models
575V models
60V
DC
80V
DC
180.0
200.0
360.0
400.0
470.0
480.0
690V models
100V
DC
100V
DC
120V
DC