Configuring The Ied And Changing Settings; Overview; Configuring Analog Ct Inputs - ABB RELION 650 Series Commissioning Manual

Hide thumbs Also See for RELION 650 Series:
Table of Contents

Advertisement

1MRK 506 366-UEN A
Section 5
5.1

Overview

The customer specific values for each setting parameter and a configuration file have to be
available before the IED can be set and configured, if the IED is not delivered with a
configuration.
Use the configuration tools in PCM600 to verify that the IED has the expected configuration.
Each function included in the IED has several setting parameters, which have to be set in order
to make the IED behave as intended. A factory default value is provided for each
parameter.The Parameter Setting Tool in PCM600 is used when changing setting parameters.
All settings can be
Entered manually through the local HMI.
Written from a PC, either locally or remotely using PCM600. Front or rear port
communication has to be established before the settings can be written to the IED.
The IED uses a FLASH disk for storing configuration data and process data like counters,
object states, Local/Remote switch position etc. Since FLASH memory is used, measures have
been taken in software to make sure that the FLASH disk is not worn out by too intensive
storing of data.
This means, that to be absolutely sure that all data have been saved to FLASH, it is necessary
to leave the IED with auxiliary power connected after all the commissioning is done (including
setting the Local/Remote switch to the desired position) for at least one hour after the last
commissioning action performed on the IED.
After that time has elapsed, it will be safe to turn the IED off, no data will be lost.
5.2

Configuring analog CT inputs

The analog input channels must be configured to get correct measurement results as well as
correct protection functionality. Because all protection algorithms in the IED utilize the
primary system quantities, it is extremely important to make sure that connected current
transformer settings are done properly. These data are calculated by the system engineer and
normally set by the commissioner from the local HMI or from PCM600.
The analog inputs on the transformer input module are dimensioned for either 1A or 5A. Each
transformer input module has a unique combination of current and voltage inputs. Make sure
the input current rating is correct and that it matches the order documentation.
The primary CT data are entered via the HMI menu under Main menu/Configurations/Analog
modules
Commissioning manual
Configuring the IED and changing
settings
Make sure that the DC supply is not turned off when the IED saves the written
configuration.

Configuring the IED and changing settings

Section 5
M11730-2 v6
M12312-6 v8
39

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rel650

Table of Contents