Direct Start From The Operating System; Indirect Start Via Wago-I/O-Check From The Configuration Program (Device Level Tci Conformance Class 2); Indirect Start Via Wago-I/O-Check From The Configuration Program (Module Level Tci Conformance Class 2); Direct Start From The Configuration Program (Device Level Tci Conformance Class 3) - WAGO 750-666/000-003 Manual

Wago-i/o-system 750 4fdi/2fdo 24v/10a profisafe v2 ipar, 4-channel digital input and 2-channel digital output module profisafe v2 ipar, 24v/10a semiconductor power output
Hide thumbs Also See for 750-666/000-003:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iPar
7.4.4.1

Direct Start from the Operating System

In the Windows Start menu, select the entry Programs  WAGO-Software 
WAGO-I/O-CHECK 3  WAGO-Safety-Editor 75x.
The Safety Editor is started in OFFLINE mode.
7.4.4.2
Indirect Start via WAGO-I/O-CHECK from the Configuration Program
(Device Level TCI Conformance Class 2)
In the configuration program of the safe PLC, select a device (fieldbus coupler)
and from the "WAGO-I/O-CHECK 3" TCI link, start the WAGO-I/O-CHECK.
The configuration program passes the current language and communication
setting to WAGO-I/O-CHECK.
Select a PROFIsafe I/O module for parameterization in the fieldbus node
configuration displayed in WAGO-I/O-CHECK. WAGO-I/O-CHECK then starts
WAGO Safety Editor 75x with the current language and communication setting.
The Safety Editor is started in ONLINE mode.
Communication occurs over the serial connection for a PROFIBUS fieldbus
coupler and over Ethernet for a PROFINET fieldbus coupler.
If you want to exit the parameterization of the PROFIsafe I/O module and to close
the Safety Editor, then WAGO-I/O-CHECK is also closed.
7.4.4.3
Indirect Start via WAGO-I/O-CHECK from the Configuration Program
(Module Level TCI Conformance Class 2)
In the configuration program, select a PROFIsafe I/O module and from the
"WAGO-I/O-CHECK 3" TCI link, start the WAGO-I/O-CHECK. The
configuration program passes the current language and communication setting to
WAGO-I/O-CHECK. WAGO-I/O-CHECK then starts WAGO Safety Editor 75x
with the current language and communication setting. The Safety Editor is started
in ONLINE mode. Communication occurs over the serial connecting cable for a
PROFIBUS fieldbus coupler and via the TCP/IP connection for a PROFINET
fieldbus coupler.
If you want to exit the parameterization of the PROFIsafe I/O module and to close
the Safety Editor, then WAGO-I/O-CHECK remains open.
7.4.4.4
Direct Start from the Configuration Program (Device Level TCI
Conformance Class 3)
In the configuration program of the safe PLC, select a device (fieldbus coupler)
and from the "WAGO-Safety-Editor 75x" TCI link, start the WAGO-Safety-
Editor 75x. The configuration program passes the current language and
communication setting to the Safety Editor. Because no module (PROFIsafe I/O
module) is selected for parameterization, the Safety Editor is automatically closed
after an appropriate message is displayed.
Manual
Version 1.2.0, valid from HW/SW Version 01/01
Commissioning
99