Changes To Basic Parameters (01) Group - Delta CP2000 Series Quick Start Manual

Fan/pump vector control drive
Hide thumbs Also See for CP2000 Series:
Table of Contents

Advertisement

Parameter
Display Text
00-32 Keypad
KPD STOP
stop function
ENABLE

Changes to Basic Parameters (01) group

Parameter
Display Text
01-11 Output
Lower Bound
frequency lower
FREQ
limit
01-12
1st ACC Time
Acceleration time
1
01-13
1st DEC Time
Deceleration time
1
3-5 Setting Up Parameters for the First Time | CP2000
Description of Parameter
This determines whether the
STOP key on the keypad is
active when the drive is
running in AUTO mode.
Parameter options:
0 – STOP key disabled.
1 – STOP key enabled
(preferred for safety)
Description of Parameter
This determines the
minimum speed of the drive
motor. It is important that
this speed is not too low to
prevent motor overheating.
This is the time, in seconds,
for the drive to ramp up from
0 Hz to 60 Hz. It's important
that this time is not too fast,
or an overload fault will trip.
The factory default time is
too low.
This is the time, in seconds,
for the drive to ramp down
from 60 Hz to 0 Hz. If this
time is set too low, an OVN
fault will occur. The factory
default time is too low for
large inertia loads like
centrifugal fans.
9
Default
Preferred
Value
Value
0
1
Default
Preferred
Value
Value
0.00 Hz
10-15 Hz
10 secs
60 secs
10 secs
60 secs