V Series - Delta C2000 Series User Manual

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

Chapter 9 Specifications

9-2 460V Series

Frame Size
Model VFD-_ _ _ C_ _
Applicable Motor Output(kW)
Applicable Motor Output(HP)
Rated Output Capacity
(kVA)
Rated Output Current
(A)
Carrier Frequency
(kHz)
Rate Output Capacity
(kVA)
Rated Output Current
(A)
Carrier Frequency
(kHz)
Input Current (A) Heavy
Duty
Input Current (A)
Normal Duty
Rated Voltage/Frequency
Operating Voltage Range
Frequency Tolerance
AC Drive Weight
Cooling method
Braking Chopper
DC reactor
EMI Filter
EMC-COP01
Frame Size
Model VFD-_ _ _ C_ _
Applicable Motor Output(kW)
Applicable Motor Output(HP)
Rated Output Capacity
(kVA)
Rated Output Current
(A)
Carrier Frequency
(kHz)
Rate Output Capacity
(kVA)
Rated Output Current
(A)
Carrier Frequency
(kHz)
Input Current (A) Heavy Duty 108
Input Current (A)
Normal Duty
Rated Voltage/Frequency
Operating Voltage Range
Frequency Tolerance
AC Drive Weight
Cooling method
Braking Chopper
DC reactor
EMI Filter
EMC-COP01
NOTE
The value of the carrier frequency is a factory setting. To increase the carrier frequency, the current needs to be decreased. See derating
curve diagram of Pr06-55 for more information.
When the control mode is FOC senrorless, TQC+PG, TQC sensorless, PM+PG and PM sensorless, the current needs to be decreased. For
more information see Pr06-55.
When a load is a shock or impact load, use a higher level model.
For FRAME A, B and C, Model VFDXXXC43A the enclosure type is IP20/NEMA1/UL TYPE1.
For FRAME D and above, if the last character of the model is A then the enclosure type is IP20 but the wiring terminal is IP00; if the last
character of the model is E, the enclosure type is IP20/NEMA1/UL TYPE1.
C2000 Series
A
007
015
022
037
0.75
1.5
2.2
3.7
1
2
3
5
2.3
3.0
4.5
6.5
2.9
3.8
5.7
8.1
2.4
3.2
4.8
7.2
3.0
4.0
6.0
9.0
2~15kHz (8kHz)
4.1
5.6
8.3
13
4.3
5.9
8.7
14
2.6± 0.3Kg
Natural cooling
Frame A to C (built-in); Frame D and above (optional)
Frame A to C (optional); Frame D and above (built-in)
VFDXXXC43A Frame A to C: No EMI Filter; VFDXXXC43E: Built-in EMI Filter
VFDXXXC43A/43E Frame D and above: EMI Filter is optional
D
E
550
750
900
1100
55
75
90
110
75
100
125
150
84
114
136
167
105
143
171
209
88
120
143
175
110
150
180
220
2~10kHz (6kHz)
149
159
197
114
157
167
207
3-phase AC 380V~~480V (-15% +10%), 50/60Hz
38.5± 1.5Kg
64.8± 1.5Kg
Frame A to C (built-in); Frame D and above (optional)
Frame A to C (optional); Frame D and above (built-in)
VFDXXXC43A Frame A to C: No EMI Filter; VFDXXXC43E: Built-in EMI Filter
VFDXXXC43A/43E Frame D and above: EMI Filter is optional
VFDXXC43A (optional); VFDXXXC43E (built-in)
B
040
055
075
110
4.0
5.5
7.5
11
5
7.5
10
15
7.6
9.6
14
18
9.5
11
17
23
2~6kHz (2kHz)
8.4
10
14
19
10.5
12
18
24
14.5
16
19
25
15.5
17
20
26
3-phase AC 380V~480V ( -15%~+10%), 50/60Hz
323~528Vac
47~63Hz
5.4± 1Kg
Fan cooling
VFDXXC43A (optional); VFDXXXC43E (built-in)
F
1320
1600
1850
2200
132
160
185
220
175
215
250
300
197
235
280
348
247
295
352
437
2~6kHz (2kHz)
207
247
295
367
260
310
370
460
228
285
361
380
240
300
380
400
323~528Vac
47~63Hz
86.5± 1.5Kg
134± 4Kg
Fan cooling
9-2
C
150
185
220
300
15
18.5
22
30
20
25
30
40
24
29
34
45
30
36
43
57
25
30
36
48
32
38
45
60
2~10kHz (6kHz)
33
38
45
60
35
40
47
63
9.8± 1.5Kg
G
H
2800
3150
3550
4500
280
315
355
450
375
420
475
600
417
466
517
677
523
585
649
816
438
491
544
720
550
616
683
866
2~9kHz (4kHz)
469
527
594
816
494
555
625
866
228Kg
D0
370
450
37
45
50
60
55
69
69
86
58
73
73
91
70
96
74
101
27± 1 Kg

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents