STO Alarm Latch
Settings
0: STO alarm Latch
1: STO alarm no Latch
Pr06-44=0 STO Alarm Latch: after the reason of STO Alarm is cleared, a Reset command is need
to clear STO Alarm.
Pr06-44=1 STO Alarm no Latch: after the reason of STO Alarm is cleared, the STO Alarm will be
cleared automatically.
All of STL1~STL3 error are "Alarm latch" mode (in STL1~STL3 mode, the Pr06-44 function is no
effective).
Treatment to Output Phase Loss (OPHL)
Settings
0: Warn and keep operating
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning
The OPHL protect will be active when the setting is not 3.
Deceleration Time of Output Phase Loss
Settings
0.000~65.535 sec
Current detection level of output phase loss
Settings
0.00~655.35%
Output phase loss detection function executing time before run
Settings
0.000~65.535 sec
When Pr06-48 is 0, OPHL detection function will be disabled
Chapter 12 Description of Parameter Settings C2000 Series
12-06-16
Factory Setting: 0
Factory Setting: 3
Factory Setting:0.500
Factory Setting:1.00
Factory Setting:0.000