Status 3: Motor drive is in stop; Pr06-48 0 ; Pr07-02 0
When motor drive starts, it will perform Pr06-48 and then Pr07-02 (DC brake). DC brake current
level in this status includes two parts, one is 20 times of Pr06-47 setting value in Pr06-48 setting
time, and Pr07-02 setting value in Pr07-01 setting time. Total DC brake time is
T=Pr06-48+Pr07-02.
In this period, if OPHL happens, motor drive starts to count until Pr06-48/2, motor drive will
perform Pr06-45 setting.
Sta tus 3-1: P r0 6-48 0, Pr07 -0 2 0 (No OPHL d e tected be fore ope ra tion )
Operat io n co mman d
OP HL det ect ion ac tion
O PHL detec tion
20 *[ Pr0 6-4 7 ]
Pr.07-01
Pr.06-47
Out put current
Sta tus 3-2: P r0 6-48 0, Pr07 -0 2 0 (OPHL d ete cte d befo re o perati on)
O peration command
OP HL de tection action
OPHL det ect ion
20 *[Pr06-47]
Outp ut current
Chapter 12 Description of Parameter Settings C2000 Series
Driv e's s tat us
OPHL det ect io n ac ts
No OPHL detec ted
Pr. 06-48
Total DC brak e time
Drive's st atus
OPHL dete ction act s
O PHL detected
DC brake c om mand
P r.07 -01
Actual output c urrent
P r.06 -47
Pr. 06- 48
2
Pr.06 -48
Tota l DC brake time
12-06-18
Start to op era te
Pr. 07-02
Whe n OPHL, Pr06-45 act s
P r.07 -02
S tart to ope ra te
Time
Time