Frequency Point when switch from I/F mode to PM Sensorless mode
Settings
0.00~600.00Hz
Frequency Point when switch from PM Sensorless Observation mde to I/F mode
Settings
0.00~600.00Hz
I/F mode, low pass-filter time
Settings
0.0~6.0 sec
Initial Angle Detection Time
Settings
0~20 ms
PM Sensorless (I/f + FOC) Adjustment Procedure
1. When executing Static test for PM(IPM) (05-00=13), VFD software can be used to monitor
adjustment procedure. To download VFD Sotware go to:
http://www.delta.com.tw/product/em/download/download_main.asp?act=3&pid=1&cid=1&tpid=3
2. Testing PM High Frequency Standstill VFD (calculating of Rs, Ld, Lg)
Procedures:
A.
Set control mode as VF mode (Pr00-10=0, Pr00-11=0)
B.
Output Frequency of Motor 1 (Pr01-01)
C.
Output Voltage of Motor 1 (Pr01-02)
D.
Induction Motor and Permanent Magnet Motor Selection (Pr05-33=1 or 2)
E.
Full-load current of Permanent Magnet Motor(Pr05-34
F.
Set Static test for PM(IPM) (05-00=13), then run the drive.
3. Set control mode as PM sensorless Mode (Parameters 00-10=0, 00-11=6)
4. Set VFD Prameters
Pr05-35
Rated Power of Permanent Magnet Motor
Pr05-36
Rated speed of Permanent Magnet Motor
Pr05-37
Pole number of Permanent Magnet Motor
Pr05-38
Inertia of Permanent Magnet Motor
Chapter 12 Description of Parameter Settings C2000 Series
0 :Start by IF mode
1: Start by VF mode
0 :Stop by IF mode
1 :Stop by VF mode
1 : When lower than Pr10-40, ramp to stop
12-10-8
Description
Factory Setting: 20.00
Factory Setting: 20.00
Factory Setting: 0.2
Factory Setting: 5