mbient Temperature derating Curve for Advanced Control Mode
A
PT100 Detection Level 1
Settings
PT100 Detection Level 2
Settings
Make sure Pr. 06-57 > Pr.06-56.
PT100 Level 1 Frequency Protection
Settings
PT100 activation level delay time
Settings
PT100 operation
Use AVI, AUI or ACI(set to 0-10V) for analog voltage input and select PT100 mode.
(1)
Choose one of the analog voltage input type: (a)AVI (Pr.03-00=11), (b) AUI (Pr.03-02=11), or
(2)
(c) ACI (Pr.03-01=11 and Pr.03-29=1).
When using ACI as analog voltage input, set Pr.03-01=11 and Pr.03-29=1. Then switch SW2
(3)
to 0-10V on the I/O control terminal block.
Set Pr.03-23=23 and AFM2 to constant current output. Switch AFM2 (SW2) to 0-20mA on the
(4)
I/O control terminal block and set constant current output to 9mA by setting Pr.03-33=45. The
AFM2 constant output current is 20mA * 45% = 9mA.
Pr.03-33 is for adjusting the constant voltage or constant current of AFM2, the setting range is
(5)
0~100.00%.
0.000~10.000V
0.000~10.000V
0.00~600.00 Hz
0~6000 sec
12-06-25
Chapter 12 Description of Parameter Settings C2000 Series
Factory Setting:5.000
Factory Setting: 7.000
Factory Setting: 0.00
Factory Setting: 60 sec