Settings
Functions
15
PID Feedback Error
16
Slip Error (oSL)
Terminal Count Value
17
Attained (Pr.02-20; not
return to 0)
Preliminary Counter
18
Value Attained
(Pr.02-19; returns to 0)
External Base Block
19
input (B.B.)
20
Warning Output
21
Over-voltage Warning
Over-current Stall
22
Prevention Warning
Over-voltage Stall
23
prevention Warning
Operation Mode
24
Indication
25
Forward Command
26
Reverse Command
Output when Current >=
27
Pr.02-33
Output when Current <
28
Pr.02-33
Output when frequency
29
>= Pr.02-34
Output when Frequency
30
< Pr.02-34
Y-connection for the
31
Motor Coil
-connection for the
32
Motor Coil
Zero Speed (actual
33
output frequency)
Zero Speed with Stop
34
(actual output frequency)
Error Output Selection 1
35
(Pr.06-23)
Error Output Selection 2
36
(Pr.06-24)
Error Output Selection 3
37
(Pr.06-25)
Error Output Selection 4
38
(Pr.06-26)
Position Attained
39
(Pr.10-19)
Speed Attained
40
(including zero speed)
Chapter 12 Description of Parameter Settings C2000 Series
Active when the feedback signal is abnormal.
Active when the slip error is detected.
Active when the counter reaches Terminal Counter Value
(Pr.02-19). This contact won't active when Pr.02-20>Pr.02-19.
Active when the counter reaches Preliminary Counter Value
(Pr.02-19).
Active when the output of the AC motor drive is shut off during
base block.
Active when the warning is detected.
Active when the over-voltage is detected.
Active when the over-current stall prevention is detected.
Active when the over-voltage stall prevention is detected.
Active when the operation command is controlled by external
terminal. (Pr.00-21 0)
Active when the operation direction is forward.
Active when the operation direction is reverse.
Active when current is >= Pr.02-33.
Active when current is < Pr.02-33
Active when frequency is >= Pr.02-34.
Active when frequency is <Pr.02-34.
Active when PR.05-24=1, when frequency output is lower than
Pr.05-23 minus 2Hz, continues longer than 05-25.
Active when PR.05-24=1, when frequency output is higher than
Pr.05-23 plus 2Hz, continues longer than 05-25.
Active when the actual output frequency is 0. (the drive should be
at RUN mode)
Active when the actual output frequency is 0 or Stop.
Active when Pr.06-23 is ON.
Active when Pr.06-24 is ON.
Active when Pr.06-25 is ON.
Active when Pr.06-26 is ON.
Active when the PG position control point reaches Pr.10-19.
Active when the output frequency reaches frequency setting or
stop.
12-02-15