AVI Low Point
Settings
AVI Proportional Low Point
Settings
AVI Mid Point
Settings
AVI Proportional Mid Point
Settings
AVI High Point
Settings
AVI Proportional High Point
Settings
When Pr.03-28 = 0, AVI setting is 0-10V and the unit is in voltage (V).
When Pr.03-28
0, AVI setting is 0-20mA or 4-20mA and the unit is in current (mA).
When setting analog input AVI to frequency command, it 100% corresponds to Fmax (Pr.01-00
Max. operation frequency).
The 3 parameters (Pr03-51, Pr03-53 and Pr03-53) must meet the following argument: P03-51 <
P03-53 < P03-55. The 3 proportional points (Pr03-52, Pr03-54 and Pr03-56) doesn't have any limit.
Between two points is a linear calculation. The ACI and AUI are same as AVI.
The output % will become 0% when the AVI input value is lower than low point setting.
For example:
P03-51 = 1V; P03-52 = 10%. The output will become 0% when AVI input is lower than 1V. If the AVI
input is swing between 1V and 1.1V, drive's output frequency will beats between 0% and 10%
ACI Low Point
Settings
ACI Proportional Low Point
Settings
03-28=0, 0.00~10.00V
03-28 0, 0.00~20.00mA
0.00~100.00%
03-28=0, 0.00~10.00V
03-28 0, 0.00~20.00mA
0.00~100.00%
03-28=0, 0.00~10.00V
03-28 0, 0.00~20.00mA
0.00~100.00%
Pr.03-29=1, 0.00~10.00V
Pr.03-29 1, 0.00~20.00mA
0.00~100.00%
12-03-25
Chapter 12 Description of Parameter Settings C2000 Series
Factory Setting: 0.00
Factory Setting: 0.00
Factory Setting: 5.00
Factory Setting: 50.00
Factory Setting: 10.00
Factory Setting: 100.00
Factory Setting: 4.00
Factory Setting: 0.00