Delta C2000 Series User Manual page 289

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

Settings
Functions
6
JOG Command
Acceleration/deceleration
7
Speed Inhibit
st
nd
The 1
, 2
acceleration
8
or deceleration time
selection
rd
th
The 3
, 4
acceleration
9
or deceleration time
selection
EF Input
10
(EF: External fault)
External B.B. Input
11
(Base Block)
Chapter 12 Description of Parameter Settings C2000 Series
This function is valid when the source of operation command is
external terminals.
Before executing this function, it needs to wait for the drive stop
completely. During running, it can change the operation direction
and STOP key on the keypad is valid. Once the external terminal
receives OFF command, the motor will stop by the JOG
deceleration time. Refer to Pr.01-20~01-22 for details.
When this function is enabled, acceleration and deceleration is
stopped. After this function is disabled, the AC motor drive starts
to accel./decel. from the inhibit point.
The acceleration/deceleration time of the drive could be selected
from this function or the digital status of the terminals; there are 4
acceleration/deceleration speeds in total for selection.
For external fault input. Motor drive will decelerate by Pr.07-20
setting, keypad will show EF. (It will have fault record when external
fault occurs). Until the causes of fault are eliminated, the drive can
keep running after resetting.
When the contact of this function is ON, output of the drive will be
cut off immediately, and the motor will be free run and keypad will
display B.B. signal. Refer to Pr.07-08 for details.
12-02-4
Descriptions