When Pr.01-12, 01-14, 01-16, 01-18
The Actual Accel. Time = Pr.01-12, 01-14, 01-16, 01-18 + (Pr.01-24 + Pr.01-25)/2
When Pr.01-13, 01-15, 01-17, 01-19
The Actual Decel. Time = Pr.01-13, 01-15, 01-17, 01-19 + (Pr.01-26 + Pr.01-27)/2
Frequency
Skip Frequency 1 (upper limit)
Skip Frequency 1 (lower limit)
Skip Frequency 2 (upper limit)
Skip Frequency 2 (lower limit)
Skip Frequency 3 (upper limit)
Skip Frequency 3 (lower limit)
Settings
0.00~600.00Hz
These parameters are used to set the skip frequency of the AC drive. But the frequency output is
continuous. There is no limit for the setting of these six parameters and can be used as required.
The skip frequencies are useful when a motor has vibration at a specific frequency bandwidth. By
skipping this frequency, the vibration will be avoided. It offers 3 zones for use.
These parameters are used to set the skip frequency of the AC drive. But the frequency output is
continuous. The limit of these six parameters is 01-28 01-29 01-30 01-31 01-32 01-33. This
function will be invalid when setting to 0.0.
The setting of frequency command (F) can be set within the range of skip frequencies. In this
moment, the output frequency (H) will be limited by these settings.
When accelerating/decelerating, the output frequency will still pass the range of skip frequencies.
Chapter 12 Description of Parameter Settings C2000 Series
Pr.01-24 and Pr.01-25,
Pr.01-26 and Pr.01-27,
01-25
01-24
12-01-9
01-26
Time
01-27
Factory Setting: 0.00