dEb Return Time
Settings
0.0~25.0 sec
dEb (Deceleration Energy Backup) let motor drive decelerates to stop when momentary power loss
occurs.
dEb se tting l evel
Lv setti ng le ve l
So ft start rel ay o f p owe r side
Ou tput f requ ency
Dwell Time at Accel.
Settings
0.00~600.00 sec
Dwell Frequency at Accel.
Settings
0.00~600.00Hz
Dwell Time at Decel.
Settings
0.00~600.00 sec
Dwell Frequency at Decel.
Settings
0.00~600.00 Hz
In the heavy load situation, Dwell can make stable output frequency temporarily, such as crane or
elevator.
Pr.07-15 to Pr.07-18 is for heavy load to prevent OV or OC occurs.
Frequency
07-16
Dwell
Frequency
at Accel.
Chapter 12 Description of Parameter Settings C2000 Series
dEb actio n
07-15
Dwell Time
at Accel.
Dwell at accel./decel.
12-07-6
Factory Setting: 0.0
Auto de ce lerati on
Factory Setting: 0.00
Factory Setting: 0.00
Factory Setting: 0.00
Factory Setting: 0.00
07-18
Dwell
07-17
Frequency
Dwell Time
at Decel.
at Decel.
Time