Zero-speed Level of Motor
Settings
0~65535 rpm
This parameter should be used with the multi-function output terminals (set to 43). It needs to be
used with PG cared and motor with encoder feedback.
This parameter is used to set the level of motor zero-speed. When the actual speed is lower than
this setting, the corresponding multi-function output terminal 43 will be ON as shown as follows.
Max. Frequency of Resolution Switch
Settings
0.00~600.00Hz
Switch the delay time of Max. output frequency
Settings
0.000~65.000 sec.
It is used to improve the unstable speed or unstable position due to the insufficient of analog
resolution. It needs to be used with external terminal (set to 43). After setting this parameter, it needs
to adjust the analog output resolution of controller simultaneously by this setting.
Chapter 12 Description of Parameter Settings C2000 Series
12-02-23
Factory Setting: 0
Factory Setting: 60.00
Factory Setting: 0.000