Delta C2000 Series User Manual page 313

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

Multi-function output terminal: Function 42: Brake Current Checking Point
Settings
0~150%
Multi-function output terminal: Function 42: Brake Frequency Checking Point
Settings
0.00~655.35Hz
Pr02-32, Pr02-33, Pr02-34, Pr02-57 and Pr02-58 can be applied on setting up cranes. (Choose
crane action #42 to set up multi-function output Pr02-13, Pr02-14, Pr02-16, and Pr02-17)
When output current of a drive is higher than the setting of Pr02-33 Pivot Point of the Current
(>=02-33) and when output frequency is higher than the setting of Pr02-34 Pivot Point of the
Frequency (>= 02-34), choose #42 to set up Multi-function output Pr02-13, Pr02-14, Pr02-16 and
Pr002-17 after the delay time set at Pr02-32.
When the Pivot Point of the Current 's setting 02-57 0 and when the output current of the drive is
lower than the setting of Pr02-57 (<02-57), or when the output frequency is lower than the setting of
Pr02-58 (<02-58), the disable the setting #42 of the multi-function output Pr02-13, Pr02-14,
Pr02-16, Pr02-17
When Pr02-57 = 0, the output current is lower than setting of Pr02-33 Pivot Point of the current
(<02-33) or when output frequency is lower than the setting of Pr02-58(<02-58), disable the setting
of #42 of the multi-function output Pr02-13, Pr02-14, Pr02-16, Pr02-17.
IO Card Type
Settings
Read only
0: No IO Card
1: EMC-BPS01 Card
2: No IO Card
3: No IO Card
4: EMC-D611A Card
5: EMC-D42A Card
6: EMC-R6AA Card
7: No IO Card
Chapter 12 Description of Parameter Settings C2000 Series
12-02-28
Factory setting: 0
Factory setting: 0.00
Factory setting: Read only