Delta C2000 Series User Manual page 314

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

03 Analog Input/Output Parameter
Analog Input Selection (AVI)
Analog Input Selection (ACI)
Analog Input Selection (AUI)
Settings
0: No function
1: Frequency command (speed limit under torque control mode)
2: Torque command (torque limit under speed mode)
3: Torque offset command
4: PID target value
5: PID feedback signal
6: PTC thermistor input value
7: Positive torque limit
8: Negative torque limit
9: Regenerative torque limit
10: Positive/negative torque limit
11: PT100 thermistor input value
12: Reserved
13: PID compensation value
14~20: Reserved
When use analog input as PID reference value, Pr00-20 must set 2(analog input).
Setting method 1: Pr03-00~03-02 set 1 as PID reference input
Setting method 2: Pr03-00~03-02 set 4 as PID reference input
If the setting value 1 and set value 4 existed at the same time, AVI input has highest priority to
become PID reference input.
When use analog input as PID compensation value, Pr08-16 must set 1(Source of PID
compensation is analog input). The compensation value can be observed via Pr08-17.
When it is frequency command or TQC speed limit, the corresponding value for 0~±10V/4~20mA is
0 – max. output frequency(Pr.01-00)
When it is torque command or torque limit, the corresponding value for 0~±10V/4~20mA is 0 – max.
output torque (Pr.11-27).
When it is torque compensation, the corresponding value for 0~±10V/4~20mA is 0 – rated torque.
Chapter 12 Description of Parameter Settings C2000 Series
This parameter can be set during operation.
12-03-1
Factory Setting: 1
Factory Setting: 0
Factory Setting: 0