API
CANRX
261
P
Bit device
X
Y
M
K
S1
S2
S3
D
Notes on operand usage: none
S1
D
The CANRX command can read the index of the corresponding slave station.
When it is executed, it will send the SDO message format to the slave station.
M1066 and M1067 will both be 0 at that time, and M1066 will be set as 1 after
reading. If the slave station gives the correct response, it will write the value to the
preset register, and set M1067 as 1. If the slave station has a response error,
M1067 will be set as 0, and an error message will be recorded to D1076 to
D1079.
M1002: When the PLC runs, the command will be triggered once and will set
K4M400 = K1
Afterwards, each time M1066 is 1, it will switch to a different message.
S1
S2
S3
D
Word device
H
KnX KnY KnM
T
: Slave station number.
: Preset address.
Read CANopen slave station data
16-bit command (9 STEP)
CANRX
Continuous
C
D
execution type
32-bit command
Flag signal
S2
: Main index..
16-115
PLC Function Applications
CANRXP
Pulse
execution type
S3
: Subindex+bit length.