Delta C2000 Series User Manual page 256

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

Coefficient Gain in Actual Output Frequency
Settings 0~160.00
This parameter is to set coefficient gain in actual output frequency. Set Pr.00-04= 31 to display the
calculation result on the screen (calculation = output frequency * Pr.00-05).
Software Version
Settings Read only
Parameter Protection Password Input
Settings 1~9998, 10000~65535
Display
0~3 (the times of password attempts)
This parameter allows user to enter their password (which is set in Pr.00-08) to unlock the
parameter protection and to make changes to the parameter.
Pr.00-07 and Pr.00-08 are used to prevent the personal mis-operation.
When the user have forgotten the password, clear the setting by input 9999 and press ENTER key,
then input 9999 again and press Enter within 10 seconds. After decoding, all the settings will return
to factory setting.
Parameter Protection Password Setting
Settings 1~9998, 10000~65535
0: No password protection / password is entered correctly (Pr00-07)
1: Password has been set
To set a password to protect your parameter settings. In the first time, password can be set directly.
After setting, the value of 00-08 will become 1, which means password protection is activated.
When the password is set, if any parameter setting needs to be changed, be sure to enter correct
password in 00-07, and then the password will be inactivated temporarily with 00-08 changing to 0.
At this time, parameters setting can be changed. After setting, re-power the motor drive, and
password will be activated again.
To cancel the password protection, after entering correct password in 00-07, 00-08 also needs to be
set as 0 again to inactive password protection permanently. If not, password protection will be
active after motor drive re-power.
The keypad copy function will work normally only when the password protection is inactivated
temporarily or permanently, and password set in 00-08 will not be copied to keypad. So when
copying parameters from keypad to motor drive, the password need to be set manually again in
the motor drive to active password protection.
Chapter 12 Description of Parameter Settings C2000 Series
12-00-5
Factory Setting: 0
Factory Setting: #.#
Factory Setting: 0
Factory Setting: 0