Delta C2000 Series User Manual page 312

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

For Example:
If the value of Pr.02-53 displays 0003h (Hex), it means RY1and RY2 are used by PLC.
Display the Frequency Command Executed by External Terminal
Settings
Read only
When the source of frequency command comes from the external terminal, if Lv or Fault occurs at
this time, the frequency command of the external terminal will be saved in this parameter.
Reserved
Release Brake Check
Settings
0.000~65.000 sec.
The parameter needs to be used with MI=55. This is to be set for the time difference of
mechanical brake delay time and actual brake operation.
FWD ru n
comma nd
Out put
frequ ency
MO= 63
MI= 55
Chapter 12 Description of Parameter Settings C2000 Series
Ou tput frequency> =Pr02 -3 4
and output curren t>= Pr0233
Pr02-32, brake delay time
Mechanical d ela y time
P r02-56, brake-release ch ecking time
12-02-27
Factory Setting: Read only
Factory Setting: 0.000
No checking signal when
brake-release che ckin g time
is reach ed.