Terminal Counting Value Attained (return to 0)
Settings
0~65500
The counter trigger can be set by the multi-function terminal MI6 (set Pr.02-06 to 23). Upon
completion of counting, the specified multi-function output terminal will be activated (Pr.02-13~02-14,
Pr.02-36, 02-37 is set to 18). Pr.02-19 can't be set to 0.
When the display shows c5555, the drive has counted 5,555 times. If display shows c5555 , it
means that real counter value is between 55,550 to 55,559.
Preliminary Counting Value Attained (not return to 0)
Settings
0~65500
When the counter value counts from 1 and reaches this value, the corresponding multi-function
output terminal will be activated, provided one of Pr. 02-13, 02-14, 02-36, 02-37 set to 17
(Preliminary Count Value Setting). This parameter can be used for the end of the counting to make
the drive runs from the low speed to stop.
Digital Output Gain DFM
Settings
1~166
It is used to set the signal for the digital output terminals (DFM-DCM) and digital frequency output
(pulse X work period=50%). Output pulse per second = output frequency X Pr.02-21.
Desired Frequency Attained 1
Settings
0.00~600.00Hz
The Width of the Desired Frequency Attained 1
Settings
0.00~600.00Hz
Desired Frequency Attained 2
Settings
0.00~600.00Hz
The Width of the Desired Frequency Attained 2
Settings
0.00~600.00Hz
Chapter 12 Description of Parameter Settings C2000 Series
12-02-20
Factory Setting: 0
Factory Setting: 0
Factory Setting: 1
Factory Setting: 60.00/50.00
Factory Setting: 2.00
Factory Setting: 60.00/50.00
Factory Setting: 2.00