Full-load Current of Induction Motor 1 A
Settings
10 to 120% of drive's rated current
This value should be set according to the rated current of the motor as indicated on the motor
nameplate. The factory setting is 90% X rated current.
Example: The rated current for 7.5HP (5.5kW) is 25 and factory setting is 22.5A. The range for
setting will be 10~30A.(25*40%=10A and 25*120%=30A)
Rated Power of Induction Motor 1(kW)
Settings
0~655.35 kW
It is used to set rated power of the motor 1. The factory setting is the power of the drive.
Rated Speed of Induction Motor 1 (rpm)
Settings
0~65535
It is used to set the rated speed of the motor according to the motor nameplate.
Before set up Pr05-04, this parameter must be set.
Pole Number of Induction Motor 1
Settings
2~20
It is used to set the number of motor poles (must be an even number).
Set up Pr.05-04 after setting up Pr. 01-01 and Pr.05-03 to make sure motor operate normally.
For example: the Pr05-04 factory setting range is "2~4". If use a 6 poles motor, to set up Pr01-01
and Pr05-03 according the motor nameplate, then the Pr05-04 setting range will become 2~6
automatically.
No-load Current of Induction Motor 1 (A)
Settings
0 to the factory setting in Pr.05-01
The factory setting is 40% motor rated current.
For model with 110kW and above, default setting is 20% motor rated current.
Stator Resistance(Rs) of Induction Motor 1
Rotor Resistance(Rr) of Induction Motor 1
Settings
0~65.535
Chapter 12 Description of Parameter Settings C2000 Series
12-05-4
Unit: Amper
Factory Setting: #.##
Factory Setting: #.##
Factory Setting:
1710 60Hz 4 poles
1410 50Hz 4 poles
Factory Setting: 4
Unit: Amper
Factory Setting: #.##
Factory Setting: #.###