This parameter determines the control method of the AC motor drive:
0: (IM V/f control): user can design proportion of V/f as required and can control multiple motors
simultaneously.
1: (IM V/f control + Encoder): user can use optional PG card with encoder for the closed-loop
speed control.
2: (IM Sensorless vector control): get the optimal control by the auto-tuning of motor
parameters.
3: (IM FOC vector control+ encoder): besides torque increases, the speed control will be more
accurate (1:1000).
4: (PM FOC vector control + Encoder): besides torque increases, the speed control will be more
accurate (1:1000).
5: FOC Sensorless: IM field oriented sensorless vector control
6: PM Sensorless (PM field oriented sensorless vector control)
7: IPM Sensorless (Interior PM field oriented sensorless vector control)
When 00-10=0, and set Pr.00-11 to 0, the V/F control diagram is shown as follows.
Fcm d
Pr 00-20
Accel Decel tim e
When 00-10=0, and set Pr.00-11 to 1, the V/F control + encoder diagram is shown as follows.
Fcm d
Frequency
Pr 00-20
Inaccuracy
DC BUS
Voltage
Detect
+
V/F
X
table
+
01-00,01-01
Voltage
01-02,01-03
com pensation
01-04,01-05
01-06,01-07
01-08
Voltage
+
Com mand
V/F
X
table
+
LPF
0 7-24
LPF
07-25
12-00-7
Chapter 12 Description of Parameter Settings C2000 Series
DC BUS Voltage
AVR
07- 23
Torque
LPF
Compensation
07-24
07-26
AVR
07- 23
Voltage
Compensate
Torque
compensation
07-26
Pr otection
Current Detection
IGBT
PWM
Irms
Curr ent
Detection
IGBT
PWM
Power
Factor
Irm s
Real speed
M
01-00
01-01
01-02
05-01
05-02
05-03
05-04
M