Delta C2000 Series User Manual page 589

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

API
GBIN
171
D
P
Bit device
X
Y
M
K
S
D
Notes on operand usage:
Please refer to the function specifications table for each device in
series for the scope of device usage
S: source device used to store GRAY code. D: device used to store BIN value after
transformation.
The GRAY code corresponding to the value of the device designated by S is
transformed into a BIN value, which is stored in the device designated by D.
This command will transform the value of the absolute position encoder connected
with the PLC's input and (this encoder usually has an output value in the form of
GRAY code) into a BIN value, which is stored in the designated register.
The valid range of S is as shown below; if this range is exceeded, it will be
considered an error, and the command will not execute.
16-bit command: 0~32,767
32-bit command: 0~2,147,483,647
Word device
H
KnX KnY KnM
T
When X20=On, the GRAY code of the absolute position encoder connected
with input points X0 to X17 will be transformed into BIN value and stored in
D10.
X20
GBIN
X17
GRAY CODE 6513
0 0 0 1
b15
H1971=K6513
0 0 0
GRAY code
16-bit command (5 STEP)
GBIN
Continuous
C
D
execution type
32-bit command (9 STEP)
DGBIN
Continuous
execution type
Flag signal: none
K4X0
D10
K4X0
0 1
0
1
1
1
0
0
1
1
1
0
0
1
0
1
1
1
0
16-97
PLC Function Applications
BIN transformation
GBINP
Pulse
execution type
DGBINP
Pulse
execution type
X0
0 0
1
b0
0 0 1