Reactor
Recommended Wire Size
model (Note)
8 AWG
RF008X00A
RF004X00A
4 AWG
2 AWG
RF002X00A
300 MCM
RF300X00A
Note: 600V insulated cable wire
Diagram A
Please put all wires through at least one core without winding.
Note 1: The table above gives approximate wire size for the zero phase reactors but the selection is ultimately
governed by the type and diameter of cable fitted i.e. the cable must fit through the center hole of zero phase
reactors.
Note 2: Only the phase conductors should pass through, not the earth core or screen.
Note3: When long motor output cables are used an output zero phase reactor may be required to reduce radiated
emissions from the cable.
Wiring
Method
2
8.37 mm
Diagram A
2
21.15 mm
Diagram A
2
33.62 mm
Diagram A
2
152 mm
Diagram A
R/L1
U/T1
S/L2
V/T1
T/L3
W/T1
Chapter 7 Optional Accessories C2000 Series
Qty
Corresponding motor drives
VFD007C23A; VFD015C23A; VFD022C23A;
VFD037C23A; VFD007C43A; VFD015C43A;
1
VFD022C43A; VFD037C43A; VFD040C43A
VFD055C43A
VFD055C23A; VFD075C23A; VFD110C23A;
1
VFD110C43A; VFD150C43A; VFD075C43A;
VFD110C43A; VFD150C43A
VFD150C23A; VFD185C23A; VFD220C23A;
VFD300C23A; VFD370C23A; VFD185C43A;
1
VFD220C43A; VFD300C43A; VFD370C43A;
VFD450C43A; VFD550C43A; VFD750C43A
VFD450C23A; VFD550C23A; VFD750C23A;
VFD900C23A; VFD900C43A; VFD1100C43A;
1
VFD1320C43A; VFD1600C43A; VFD1850C43A;
VFD2200C43A; VFD2800C43A; VFD3150C43A;
VFD3550C43A; VFD4500C43A
Zero Phase Reactor